When using multi-stage boilers, a selection must be made
regarding the staging order of the boiler(s). This adjustment
is made in the ADJUST menu of the control.
Lo / Hi
If the Lo/Hi staging option is selected the control stages in
sequence all of the stages in a single boiler. Once all of the
stages are turned on, the control then stages in sequence
all of the stages in the next boiler in the rotation sequence.
Lo / Lo
If the Lo/Lo staging option is selected, the control stages all
of the Lo stage outputs in all of the boilers first. Once all of
the boilers are operating on their Lo stages, the control then
operates the second stage in each boiler in the same order.
STAGING
The control operates up to nine stages to supply the
required temperature. After a stage is turned on in the firing
sequence, the control waits for the minimum time delay.
After the minimum time delay between stages has expired,
the control examines the control error to determine when
the next stage is to fire. The control error is determined
using Proportional, Integral and Derivative (PID) logic.
Proportional compares the actual supply temperature to
the boiler target temperature. The colder the supply water
temperature, the sooner the next stage is turned on.
Integral compares the actual supply temperature to the
boiler target temperature over a period of time.
Derivative compares how fast or slow the supply water
temperature is changing. If the supply temperature is
increasing slowly, the next stage is turned on sooner. If the
supply temperature is increasing quickly, the next stage is
turned on later, if at all.
FIRE DELAY
The Fire Delay is the time delay that occurs between the
time that the control closes a stage contact to fire a stage
and the burner fires for that stage. The fire delays for the
first and third stages in a boiler are adjustable using the
F DLY 1 and F DLY 2 settings. The fire delay for the sec-
ond and the fourth stages is fixed at 10 seconds, see Figure
10 below.
Fire Delay 1
Fire Delay 1 is available in all modes of operation. Fire
Delay 1 is the fire delay of the first stage of the boiler.
Fire Delay 2
Fire Delay 2 is only available in the modes of operation for
Three and Four Stage Boilers. Fire Delay 2 is the fire delay
of the third stage of the boiler.
FIG. 9
FIG. 10
7