BOILER PUMP OPERATION
In certain modes of operation, the control can operate the
individual boiler pumps on each boiler in addition to the pri-
mary pump. The boiler pump turns on prior to the boiler fir-
ing and continues to run after the boiler is turned off. The
amount of time that the boiler pump turns on prior to the
boiler firing is determined by the BOIL MASS setting. If a
BOIL MASS of Lo is selected, the boiler pump turns on 15
seconds prior to the boiler. If a BOIL MASS of Medium is
selected, the boiler pump turns on 22 seconds prior to the
boiler. If a BOIL MASS of Hi is selected, the boiler pump
turns on 30 seconds prior to the boiler. However, if the con-
trol is operating based on a set point demand, the boiler
pump turns on 5 seconds prior to the boiler, see Figure 13.
Boiler Pump Purge
The amount of time that the boiler pump continues to run
after the boiler turns off is adjustable using the boiler pump
purge setting (PURG Boil Pmp).
SECTION D: BOILER RESET OPERATION
S
ECTION D1: BOILER RESET (STAND ALONE)
BOILER DEMAND
When operating in the stand-alone mode, a boiler demand
is required in order for the control to provide heat to the
heating system. A boiler demand is generated by applying
a voltage between 24 and 230 V (ac) across the Boiler
Demand and Common Demand terminals (6 and 7)
(FIG. 14). Once voltage is applied, the Boiler Demand
pointer is displayed in the LCD. If the control is not in
WWSD, the control closes the primary pump contact. The
control calculates a boiler target supply temperature based
on the outdoor air temperature and the characterized heat-
ing curve settings.
BOILER TARGET TEMPERATURE
The boiler target temperature is determined from the char-
acterized heating curve settings and the outdoor air tem-
perature. The control displays the temperature that it is cur-
rently trying to maintain as the boiler supply temperature. If
the control does not presently have a requirement for heat,
it does not show a boiler target temperature. Instead, "- - -"
is displayed in the LCD.
CHARACTERIZED HEATING CURVE
The control varies the supply water temperature based on
the outdoor air temperature. The control takes into account
the type of terminal unit that the system is using. Since dif-
ferent types of terminal units transfer heat to a space using
different proportions of radiation, natural convection and
forced convection, the supply water temperature must be
controlled differently. Once a terminal unit is selected, the
control varies the supply water temperature according to the
9
FIG. 12
FIG. 13
FIG. 14