The MP
2
is capable of controlling the supply water tempera-
ture for up to nine ON / OFF stages based on outdoor tem-
perature, control for the Domestic Hot Water (DHW) gener-
ation, a set point requirement or optionally an external input
signal (0 - 10 V (dc)). A large easy to read display provides
current system temperatures and operating status (FIG. 1).
The control has outputs for a primary pump and a combus-
tion air damper or alarm. Based on the mode of operation
selected, the control can operate different combinations of
boiler stages and boiler pumps.
ADDITIONAL FUNCTIONS INCLUDE:
Installer and Advanced Access Levels
• Primary Pump Output
• Individual Boiler Pump Outputs (in applicable
modes)
• Pump Exercising
• Pump Purging (primary and boiler)
• Boiler Demand for Space Heating Loads
• DHW Demand for DHW Loads
• Set Point Demand for Set Point Loads
• Test Sequence to Ensure Proper Component
Operation
• Setback Input for Energy Savings
• 0 - 10 V (dc) Input Signal
Modes
1 Up to 9 On/Off Boilers
2 Up to 4 On/Off Boilers & 4 Pumps
3 Up to 4 Lo/Hi Boilers
4 Up to 3 Lo/Hi Boilers & 3 Pumps
5 Up to 3 Three Stage Boilers
6 Up to 2 Three Stage Boilers & 2 Pumps
7 Up to 2 Four Stage Boilers
8 1 Four Stage Boiler & 1 Pump
INSTALLATION INSTRUCTIONS
INS7162 Rev-
T
M
INTRODUCTION
FIG. 1
Seitenansicht 0
1 2 3 4 5 6 ... 35 36

Inhaltsverzeichnis

Seite 1 - INSTALLATION INSTRUCTIONS

The MP2is capable of controlling the supply water tempera-ture for up to nine ON / OFF stages based on outdoor tem-perature, control for the Domestic

Seite 2 - TABLE OF CONTENTS

type of terminal unit. This improves the control of the airtemperature in the building. BOILER INDOOR DESIGN TEMPERATUREThe indoor design temperature

Seite 3 - SYMBOL DESCRIPTION

HIGH MASS RADIANT (1)This type of a hydronic radiant floor is embedded in either athick concrete or gypsumpour. This heating system has alarge therma

Seite 4 - SEQUENCE OF OPERATION

SECTION E: DOMESTIC HOT WATER OPERA-TIONSECTION E1: DOMESTIC HOT WATER (DHW)DHW DEMANDA DHW Demand is required for the control to provide heatto the

Seite 5 - ROTATION

DHW MODE 4 - DHW IN PRIMARY / SECONDARY WITHPRIORITYWhen a DHW Demand is present, the Relay 9 / DHW con-tact (terminals 30 and 31) is closed and the p

Seite 6

NUMBER OF BOILERS USED FOR DHW GENERATIONThe number of boilers used for DHW generation can beselected from one to the maximum number of boilers usingt

Seite 7 - FIRE DELAY

BOILER TARGET DURING SET POINTThe boiler target temperature during a set point demand isincreased to at least the Set Point setting. This temperature

Seite 8 - RIMARY PUMP OPERATION

INPUT SIGNALThe control can accept either a 0 - 10 V (dc) signal or a 2 -10 V (dc) signal. The External Input Signal setting must beset to the proper

Seite 9 - HARACTERIZED HEATING CURVE

STEP ONE ----- GETTING READYCheck the contents of this package. If any of the contentslisted are missing or damaged, please contact your whole-saler

Seite 10 - BOIL IND

Set Point DemandTo generate a setpoint demand, a voltage between 24 V(ac) and 230 V (ac) must be applied across the Setp / DHWand Com Dem terminals (8

Seite 11

Relay 9 / DHWIf a DHW pump or DHW valve is connected to the Relay 9 /DHW contact (30 and 31) (FIG. 30), make sure the power tothe pump or valve circui

Seite 12

This instruction manual is organized into four main sections:1) Sequence of Operation, 2) Installation, 3) ControlSettings, and 4) Testing and Trouble

Seite 13

A good quality electrical test meter, capable of reading fromat least 0 - 300 V (ac) and at least 0 - 2,000,000 ohm, isessential to properly test the

Seite 14

 TEST THE OUTPUTSPrimary Pump (Prim P1)If a primary pump is connected to the Prim P1 terminal (11),make sure that power to the terminal block is off

Seite 15 - Do Not Apply Power

 CONNECTING THE CONTROLMake sure all power to the devices and terminal blocks isoff, and remove any remaining jumpers from the terminals.Reconnect th

Seite 16 - INPUT SIGNAL

The Alarm / C.A. DIP switch selects whether a combustionair damper or alarm device is to be connected to the C.A. /Alarm terminals (12 and 13) (FIG. 4

Seite 19

This item is only available if the External Input / Stand Alone DIP switch i

Seite 20 - EST THE SENSORS

Boiler MinimumBoiler MaximumFire Delay 1Fire Delay 2Co

Seite 21 - EST THE OUTPUTS

(This item is only available when DHW MODE is s

Seite 22 - DIP SWITCH SETTINGS

The control has a built-in test routine that is used to test themain control functions. The control continually monitors thesensors and displays an e

Seite 23 - FF / EXERCISE

DISPLAYBoiler DemandDHW / Setpoint DemandWWSDExternal Input SignalOffsetFIG. 2SYMBOL DESCRIPTION

Seite 24 -

The control was unable to read a piece of information storedin its memory (FIG. 53). Because of this, the control wasrequired to reload the factory s

Seite 25

The control is no longer able to read the boiler return sen-sor due to an open circuit (FIG. 59). The control will contin-ue to operate normally. Loc

Seite 26

32TYPICAL BOILER INSTALLATION

Seite 27

33TYPICAL BOILER INSTALLATION (CONTINUED)

Seite 28

34MP2Tekmar 150 ControllerTYPICAL DWH PRIORITY HEATING PACKAGE SYSTEM

Seite 30

9/04 - Printed in U.S.A.

Seite 31 - Do not apply power

The following defined terms and symbols are used through-out this manual to bring attention to the presence of hazardsof various risk levels, or to br

Seite 32 - TYPICAL BOILER INSTALLATION

COMBUSTION AIR OR ALARM CONTACTThe control has an isolated contact that can be used aseither a combustion air damper contact or an alarm contact.This

Seite 33

Resetting the Rotation SequenceTo reset the rotation sequence, set the Rotate / Off DIPswitch to the Off setting for 5 seconds and then return theDIP

Seite 34 - Tekmar 150 Controller

LO / HIORLO / LOWhen using multi-stage boilers, a selection must be maderegarding the staging order of the boiler(s). This adjustmentis made in the A

Seite 35

STAGE DELAYThe stage delay is the minimum time delay between the fir-ing of stages. After this delay has expired the control canfire the next stage i

Seite 36 - 9/04 - Printed in U.S.A

BOILER PUMP OPERATIONIn certain modes of operation, the control can operate theindividual boiler pumps on each boiler in addition to the pri-mary pump